Technical Specifications
| Output signal | DC4-20mA+HART Protocol |
| Output method | Linear outputSquare root output (can be remotely adjusted via configuration software) |
| Measurement range | Rated range 0-0.125~1.6KPa0-1.3~8KPa 0-6.2~40KPa 0-31.1~250KPa 0-0.117~1MPa 0-0.345~2.5MPa Maximum static pressure at one end6Mpa8Mpa 10Mpa 10Mpa 10Mpa 13Mpa |
| Zero point and range | The range and zero point can be adjusted using the onboard buttons or remotely using a HART handheld smart terminal. |
| Zero-point positive and negative migration | During a negative zero-point transition, the lower limit of the range must be greater than or equal to -URL; during a positive zero-point transition, the upper limit of the range must be less than or equal to +URL.The test range must be greater than or equal to the lower limit of the range. |
| Damping time constant | The time constant is adjustable, increasing in 0.1-second increments, from a minimum to 32 seconds. The default value is 0.1 seconds when the damping time is 0. |
| Ambient temperature limits | Standard type: -40 to 85℃; LCD display: -20 to 70℃ |
| Process temperature limit | -40 to 104℃ |
| Storage temperature limits | -40 to 85℃ |
| Ambient humidity | 0-95% relative humidity |
| Volume change | Less than 0.01in3 (0.16cm)3(Under zero-base calibration range reference conditions, silicone oil filling, 316L stainless steel diaphragm) |
| accuracy | Range ratio <5:1:≤±0.1 % FSRange ratio ≥5:1:≤±0.25 % FS |
| stability | % FSstability6 |
| Ambient temperature influence | -29 to 85℃ Zero-point error: 0.5%URL/56℃ Total error: (0.5%URL + 0.2% calibration range)/56℃ |
| Vibration effect | The vibration effect at 200 Hz is 0.2% URL/g in any axial direction. |
| Power supply range | 8-30VDC |
| Intrinsically safe explosion-proof | Ex ia ⅡC T6 Ga Note: Intrinsically safe must be powered via a safety barrier or intrinsically safe power supply. |
| Installation location affects | Zero drift is at most ±0.25 kPa. All zero drift can be corrected; it has no effect on the measurement range. |
| Load impact | There is no load effect unless the power supply voltage changes. |
| Load characteristics | Current-type load ≤ {(Us-12)÷0.02(Us=supply voltage)}Ω |